Power Management;Power Management SolutionElectroMaster;ElectroMaster;ElectroMaster Overview;ElectroMaster System Components;.;.;Powermonitor II;ElectroMaster Monitored Component;21st Century Power Monitoring Solutions;Applications and Benefits;Demand Side Management; Real time control of electrical loads to reduce energy cost.
Save money by avoiding demand penalties or participating in utility curtailment programs.
Power Control; Integrate monitoring with on site power generation.
Reduce cost through cogeneration or insure continuing operations with emergency backup.
Power Quality; Monitor the quality of electrical power.
Identify or prevent cause of unplanned shutdowns or equipment damage.;Power Quality Solutions;Power Quality Solutions;Event Log
Stored internally in non-volatile memory
Time and date stamped to nearest 0.01 seconds
100 records
Events include:
Power-up
Power-down
Relay energized
Status input active
etc....;Min/Max Log
Stored internally in non-volatile memory
Time and date stamped to nearest 0.01 seconds.
Records the minimum and maximum value for 84 different parameters;20 User Defined Setpoints
Each setpoint can be triggered by 1 of 54 parameters
20 different output actions to choose from
Oscillogram Capture
Relay Activation
Snapshot Log record
Alarm Flags
etc....;High speed pre/post trigger 7 channel oscillograph of simultaneously captured waveforms for use as a sub millisecond DFR
Continuous sampling at 10.8 kHz
Simultaneous 7 channel 2 cycle capture
Simultaneous 2 channel user defined 12 cycle capture with up to 8 cycles of pretrigger information;Spectrum Analysis
Calculates to the 41st harmonic
Accuracy of +/- 5% maintained with changing fundamental frequency throughout band from 45 to 73Hz
On board calculations
TIF
IEEE-519 Annunciation
K-factor
Crest factor
THD (IEEE and IEC);Power Quality Solutions(Stand Alone);Power Quality Solutions(Serial Communications);Power Quality Solutions(RIO Communications);Power Control Solutions;Pow